TOXALERT INT’L, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 952/472-4541 FAX 952/472-4960
www.toxalert.com
MODEL TOX-COMB/ANA
SPECIFICATIONS:
SENSOR CALIBRATION
Type: Catalytically aided platinum bead Adjustments: Zero, span
Range: 0 100 LEL Test Points: Current, voltage, output
Response: 90% in 45 seconds
Typical Life: Three years in normal service ENVIRONMENTAL (TEMPERATURE)
Zero Drift: Less than 5% per year Operating: -40° to 185° F (-40° to 85° C)
Humidity: 0- 99% RH, non condensing
ELECTRICAL DATA CONSTRUCTION
Wiring: 3 wire non-insolated Electrical Class: Class 1, Div., Groups B, C & D
Input Voltage: 11 30 VDC Mounting: Conduit or flexible cable
Input Current: 200 mA at 24 VDC Physical: 7.25” x 3.5” x 3.5”
Input Power: 2.3 W (18.4 cm x 8.9 cm x 8.9 cm)
Output: 4 to 20mA signal Weight: 1.5 pounds (0.68 kg)
Loop Resistance: 800 Ohms Housing: Cast Aluminum
Partial List of Available Combustible Gases
Acetic Acid
Acetone
Acetylene
Butane
Iso-Butane
Butene-1
iso-Butyle Alcohol
ios-Butyl Benzene
Dimethylpentane
Ethane
Ethyl Acetate
Ethyl Alcohol
Ethylene
Diethyl Ether
Dimethyl Ether
Heptane
Hexane
Hydrogen
Methane
Methyl Acetate
Methyl Alcohol
Methylethyl Ketone
Natural Gas
Octane
Pentane
Propane
Propyl Alcohol
Toluene
Xylene
JP-4 (Jet Fuel)
Available Accessories
Calibration adaptors •Remote sensor option
•Splash guards •Duct mount kit
•Calibration kits •Remote horns & strobes
ToxComb/ANA Revised 11/12 2 of 2